Q1. For a 100 kW generator, only 50 kW of load is connected. Will the generator generate only 50 kW or 100 kW?
A1.
Under steady state conditions, the (mechanical input - rotational losses) will be
equal to the electrical power output. Hence, the generator will generate only
50 kW, even though its full capacity is 100kW.
Q2. What
happens if we connect more than 100 kW of load?
A2. If we connect more than 100kW of load, there
will be flow of more current in the lines than their capacity and if present,
the fuses shall blow off. If that doesn't happen then the wires will get
overheated.
Q3. What
is the difference between "earth" and "neutral"?
A3. The
"neutral" refers to the star point in a star connection. The star
connection of the 3 phase windings of an alternator, transformer or a 3 phase
motor has one end of each phase-winding connected together, forming the neutral
point or the star point. Neutral is not present in a delta connection.
"earth" refers to the zero potential level ( the ground) to which an
electrical equipment is connected for personnel safety. The neutral of star
connection can be earth to protect the 3 phase machine for large short circuit
currents.
Q4. At
what condition, a synchronous motor acts as a synchronous condenser?
A4. When a synchronous motor is run unloaded, its
primary function becomes improving the pf pf the system, by generating or
absorbing reactive power. As we know that increasing the If changes its pf from
leading to lagging(inverted-V curve). Thus a synchronous condenser is a
synchronous motor designed with large field current. There is no shaft
extension. Larger If requires greater amount of copper and large area of cross
section of field poles as compared to ordinary synchronous motor of same
rating.
Q5. How
is a 100 MVA transformer cooled?
A5. 80 MVA -> ONAN (Oil-Natural Air-Natural)
120 MVA -> ONAF (Oil-Natural Air-Forced)
200 MVA -> OFAF (Oil-Forced Air-Forced)
250 MVA -> OPAF (Oil-Pumped Air-Forced)
Hence a 100 MVA transformer has to be ONAF(Oil-Natural Air-Forced) cooled.
"Soon I will be ready with the next five. If you want explanation on any of the above, or want to get your own question answered,or want to give a better answer to these questions, post them in the comments section below."

Thankz..itz very helpful
ReplyDeleteWhy the suply frequency in INDIA is 50HZ?
ReplyDeletebecause British people made it like that . due to 50HZ we can use thin cables ( insulation will be less ) low cost . if it is 60 HZ we have to use thick cables ( cost) . if 60 HZ like america .. all equipments will be less cost , transmission is high cost . in india transmission is less cost . equipment sizings are very cost . please correct me any one if anything wrong .
ReplyDeletesir this really help ful .but i just little confuse in synchronized motor answer ?
ReplyDeletein syncro. Moter on noload over-excited case work as syncro. Condenser which deliever leading current and improve pf.
ReplyDeleteCould you please explain how insulation is related to frequecy
ReplyDelete